QuickNet-RK Installation Instructions
4
• Twist two ground wires together.
• Heat only 1/2" of the insulated ends of the heating elements to
soften.
• While the wires are still hot, use the wire strippers to remove
1/2" of the outer insulation to expose the heating elements.
• Repeat steps 9 - 15 for other exposed heating cable end.
• Test both ends of the heating cable using this insulation resistance
test to verify there is not further damage to the heating cable.
1. Connect the ground wire to the black lead and both power
wires to the red lead of the multimeter.
2. Make sure the meter reads ‘Open’ or “OL’. If you get a different
reading, contact Tyco Thermal Controls at 800-545-6258.
3. Record these readings on the Commissioning Record (page 8).
14
15
16
17
18
13
• While the cable is still hot, use strippers to remove the outer
jacket and foil layer to expose the heating elements.
• Cut off the colored thread.
Heating elements (2)
Grounding wire (2)
Foil layer
Colored thread (1)
Outer jacket